WARNING
Risk of electric shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source.
• This product is equipped with an overload protection (fuse). A blown fuse indicates an overload or a short-circuit situation.
If the fuse blows, unplug the product and check the polarity and voltage output from the outlet. Replace the fuse as per the
servicing instructions (refer to wiring diagram for proper fuse rating) and verify the product. If the replaced fuse blows, it may
be a short-circuit and the product must be discarded or returned to an authorized service center for examination and/or repair.
!
BK
G
R
Y
R
BK
Y
NOTE 4
WALL CONTROL
WALL CONTROL
WALL CONTROL
WALL CONTROL
OVERRIDE SWITCH
OVERRIDE SWITCH
OVERRIDE LED
FURNACE BLOWER
INTERLOCK
NOTES 1, 5
NOTE 5
OPTIONAL
NOTES 5, 6
OPTIONAL
M1
X2
M2
1
2
1
123
12
4
7
6
9
3
456789
2
3
1
2
NEUTRAL
MEDIUM
HIGH
LOW
X1
GY
O
G
BL
R
GY
O
G
NC
R
(NOTE 2)
BN
BN
C1
BL
BL
DAMPER
MOTOR
MAIN EARTHING
POINT
R
O
GY
W
T1
R1
A1
DEFROST
TEMPERATURE
SENSOR
JU1
J4
J1
J3
ABCDEFG
FF IOCOLYRGB
ELECTRONIC ASSEMBLY
Y
BL
BL
Y
COM
120V 60 Hz
W1
G
BK
NEMA-15P
5-15 PLUG
BK
DOOR INTERLOCK
SWITCH S1
NO
NEUTRAL
LINE
BK
VE0037A
-t
F1
NOTE 7
W
8. WIRING DIAGRAMS
Models: 1001 ERV, 1001 HRV, 2001 ERV,
2001 HRV, ERV100HC, ERV200HC
Connection
Logic
A1
M1
M2
K1
RELAY
K2
RELAY
K5
RELAY
FAN
MOTOR
DAMPER
MOTOR
NEUTRAL
MED
NC
HIGH
LOW
J1 6
J1 3
J1 4
J1 9
K4
RELAY
J3 1
J3 2
FURNACE BLOWER INTERLOCK
CLASS 2 CIRCUIT ONLY
ELECTRONIC ASSEMBLY
S1
120V 60Hz
FROM MAIN
J1 2
J1 1
J1 8
VE0018A
NOTES
1- Controls available. See Section 7 (Low voltage only,
12 VDC).
2- The factory set wiring for blower speed selection is
high and low. Medium speed can be selected instead
of low speed. Disconnect the RED wire from the motor
RED tap and connect it to the motor BLUE tap.
3- If any of the original wire, as supplied, must be
replaced, use the same or equivalent wire.
4- Use the factory supplied protective tubing.
5- The field wiring must comply with applicable codes,
ordinances and regulations.
6- The furnace fan circuit must be class 2 circuit only.
7- SPECIFIED UL LISTED/CSA CERTIFIED LINE
FUSE. LittelFuse (225 003), 2AG Fast-Acting Fuse,
224/225 Series. Rating: 3 A.
LINE VOLTAGE
LOW VOLTAGE
AND FIELD WIRE
COLOR CODE
BK BLACK NC NO CONNECTION
BL BLUE O ORANGE
BN BROWN R RED
G GREEN W WHITE
GY GREY Y YELLOW
JUMPERS TABLE
MODEL
TYPES
DEFROST TIME
DEFROST/VENTILATION
MINUTES
JU1A JU1B JU1C JU1D JU1E JU1F JU1G
23°F
-5°C
5°F
-15°C
-17°F
-27°C
OUT OUT OUT OUT OUT IN OUT
A
LL
MODELS
6/32 6/32 6/20
NO
CHANGE
NO
CHANGE
NO
CHANGE
NO
CHANGE
NO
CHANGE
OUT
NO
CHANGE
ALL
MODELS
10/30 10/20 10/15


2
1
JU1
ABCDEF
G
FUNCTION TABLE RELAY
MODE K1 K2 K4 K5
Intermittent 0000
Exchange Low 1011
Exchange High 1111
Circulation Low 1010
Circulation High 1110
Defrost Cycle 1110
OFF 0000
0 = Relay coil is de-energized
1 = Relay coil is energized