WARNING
Risk of electric shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source.
• This product is equipped with an overload protection (fuse). A blown fuse indicates an overload or a short-circuit situation.
If the fuse blows, unplug the product and check the polarity and voltage output from the outlet. Replace the fuse as per the
servicing instructions (refer to wiring diagram for proper fuse rating) and verify the product. If the replaced fuse blows, it may
be a short-circuit and the product must be discarded or returned to an authorized service center for examination and/or repair.
!
8. WIRING DIAGRAMS (CONT'D)
BK
G
R
NOTE 4
BK TO R = LOW SPEED EXCHANGE
BK TO G = HIGH SPEED EXCHANGE
NO CONNECTION = OFF
OVERRIDE SWITCH
OVERRIDE SWITCH
OVERRIDE LED
NOTE 1
NOTES 1, 6
OPTIONAL
M1
X2
M2
1
2
1
123
12
4
7
6
9
3
45 789
2
3
1
2
NEUTRAL
MEDIUM
HIGH
LOW
X1
GY
O
G
BL
R
GY
O
G
NC
R
(NOTE 2)
BN
BN
C1
BL
BL
DAMPER
MOTOR
MAIN EARTHING
POINT
R
O
GY
W
T1
R1
A1
DEFROST
TEMPERATURE
SENSOR
JU1
J4
J1
J3
ABCDEFG
F F ICOCOLY R G B
ELECTRONIC ASSEMBLY
Y
BL
BL
Y
BK
VE0039A
-t
S2
SPDT SWITCH (ON-OFF-ON)
FAN FURNACE
INTERLOCK KIT
NOTES 5, 6
GY
BN
COM
120V 60 Hz
W1
G
NEMA-15P
5-15 PLUG
BK
DOOR INTERLOCK
SWITCH S1
NO
NEUTRAL
LINE
BK
F1
NOTE 7
W
Models: HRV100H, HRV200H
Connection
Logic
A1
M1
M2
K1
RELAY
K2
RELAY
K5
RELAY
FAN
MOTOR
DAMPER
MOTOR
NEUTRAL
MED
NC
HIGH
LOW
J1 6
J1 3
J1 4
J1 9
ELECTRONIC ASSEMBLY
S1
120V 60Hz
FROM MAIN
J1 2
J1 1
J1 8
VE0040A
NOTES
1- Controls cannot be connected to J3.
2- The factory set wiring for blower speed selection is
high and low. Medium speed can be selected instead
of low speed. Disconnect the RED wire from the motor
RED tap and connect it to the motor BLUE tap.
3- If any of the original wire, as supplied, must be
replaced, use the same or equivalent wire.
4- Use the factory supplied protective tubing.
5- Field installed option: Use only factory supplied kit.
6- The field wiring must comply with applicable codes,
ordinances and regulations.
7- SPECIFIED UL LISTED/CSA CERTIFIED LINE
FUSE. LittelFuse (225 003), 2AG Fast-Acting Fuse,
224/225 Series. Rating: 3 A.
LINE VOLTAGE
LOW VOLTAGE
AND FIELD WIRE
COLOR CODE
BK BLACK NC NO CONNECTION
BL BLUE O ORANGE
BN BROWN R RED
G GREEN W WHITE
GY GREY Y YELLOW
JUMPERS TABLE
MODEL
TYPES
DEFROST TIME
DEFROST/VENTILATION
MINUTES
JU1A JU1B JU1C JU1D JU1E JU1F JU1G
23°F
-5°C
5°F
-15°C
-17°F
-27°C
OUT OUT OUT OUT OUT IN IN
HRV100H
HRV200H
6/32 6/32 6/20
OUT OUT OUT OUT OUT OUT IN
E
XTENTED
DEFROST
ALL TYPES
10/30 10/20 10/15


2
1
JU1
ABCDEF
G
FUNCTION TABLE RELAY
MODE K1 K2 K5
Intermittent 0 0 0
Exchange Low 1 0 1
Exchange High 1 1 1
Circulation Low 1 0 0
Circulation High 1 1 0
Defrost Cycle 1 1 0
OFF 0 0 0
0 = Relay coil is de-energized
1 = Relay coil is energized