Broan HRV100H Service Manual Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 28
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
There are two methods for connecting the unit to the furnace:
Method 1: Supply side connection
Cut an opening into the furnace supply duct at least 18 inches (0.5 m) from the
furnace.
Connect this opening to the fresh air distribution port of the HRV/ERV (use metal
duct, see figure 10).
Make sure that the HRV/ERV duct forms an elbow inside the furnace ductwork
.
If desired, interlock (synchronize) the furnace blower operation with the HRV/ERV
operation. (See Section 7.4).
Method 2: Return side connection
Cut an opening into the furnace return duct not less than 10 feet (3.1 m) from the
furnace (A + B).
Connect this opening to the fresh air distribution port of the HRV/ERV (see
figure 11).
NOTE: For Method 2, it is not essential that the furnace blower runs when the HRV/ERV
is in operation, but we recommend it. If desired, synchronize the furnace
blower operation (see Section 7.4).
5.4 INSTALLING THE DUCTWORK AND REGISTERS
11
5. Installation (cont’d)
5.4.1 Fully Ducted System (as illustrated in Section 4.1)
Stale air exhaust ductwork:
Install registers in areas where contaminants are produced: kitchen, bathrooms, laundry room, etc.
Install registers 6 to 12 inches (152 to 305 mm) from the ceiling on an interior wall OR install them in the ceiling.
Install the kitchen register at least 4 feet (1.2 m) from the range top.
If possible, measure the velocity of the air flowing through the registers. If the velocity is higher than 400 ft/min. (122 m/min),
then the register type is too small. Replace with a larger one.
Fresh air distribution ductwork:
Install registers in bedrooms, dining room, living room and basement.
Install registers either in the ceiling or high on the walls with air flow directed towards the ceiling.
(The cooler air will then cross the upper part of the room, and mix with room air before descending to occupant level.)
If a register must be floor installed, direct the air flow up the wall.
5.4.2 Exhaust Ducted System (Source Point Ventilation) (as illustrated in Section 4.2)
Stale air exhaust ductwork:
(Same as for Fully Ducted System, described on Section 5.4.1)
Fresh air distribution:
WARNING
!
Never install a stale air exhaust register in a room where a combustion device is, such as a gas furnace, a gas
water heater or a fireplace.
B
A
VD0041
MINIMUM
18
(0.5 M)
METAL DUCT WITH
BACKDRAFT DAMPER
A + B = NOT LESS
THAN 10’ (3.1 M)
Figure 10
Figure 11
WARNING
!
When performing duct connection to the furnace, installation must be done in accordance with all applicable
codes and standards. Please refer to your local building code.
CAUTION
When performing connection to the furnace supply duct, this duct must be sized to support the additional
airflow produced by the HRV/ERV. Also, use a metal duct with a backdraft damper to prevent the risk of
overheating the HRV/ERV.
CAUTION
The ductwork is intended to be installed in compliance with all applicable codes.
Page view 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 27 28

Comments to this Manuals

No comments